Magnum-energy AC Load Diversion Controller (ACLD-40) Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Sensoren Magnum-energy AC Load Diversion Controller (ACLD-40) herunter. Magnum Energy AC Load Diversion Controller (ACLD-40) User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - Owner’s Manual

ACLD-40AC Load Diversion Controller - 4.0kWOwner’s Manual

Seite 2 - Contact Information

Page 3 © 2015 Sensata TechnologiesIntroductionDuring a utility power outage (see Figure 1-2): When the utility power fails, the grid-tie inverter disc

Seite 3 - SAVE THESE INSTRUCTIONS

© 2015 Sensata TechnologiesPage 4Introduction1.4 Battery Regulation MethodsIn an AC-coupled system, there are several methods that are used to regula

Seite 4 - CONSERVER CES INSTRUCTIONS

Page 5 © 2015 Sensata TechnologiesIntroduction4. Frequency disturbance/shift from the battery-based inverter: When the battery voltage rises above a m

Seite 5 - Table of Contents

© 2015 Sensata TechnologiesPage 6Introduction1.5 ACLD Features and Benefi tsThe ACLD controller is designed with features that allow easy access to wi

Seite 6 - List of Tables

Page 7 © 2015 Sensata TechnologiesIntroductionFigure 1-5, Wiring Access CoverThe left side of the ACLD controller has an access cover that can be remo

Seite 7

© 2015 Sensata TechnologiesPage 8Installation2.0 InstallationRead the entire Installation section to determine how best to install the ACLD controller

Seite 8 - 1.0 Introduction

Page 9 © 2015 Sensata TechnologiesInstallation2.1.1 Considerations when Installing the ACLD System• The ACLD controller is designed to be connected

Seite 9

© 2015 Sensata TechnologiesPage 10Installation2.2 Locating the ACLD ControllerOnly install the ACLD controller in a location that meets the following

Seite 10 - (when RE not

Page 11 © 2015 Sensata TechnologiesInstallationWALL MOUNTED(Fan facing down and MPX-CB installed)When the unit is mounted in this position, either the

Seite 11 - Introduction

© 2015 Sensata TechnologiesPage 12InstallationFigure 2-4, ACLD Dimensions and Side Reference(0.71 cm)4 placesØ.280Right SideTopSide12 ¾"(32.4 cm)

Seite 12

© 2015 Sensata TechnologiesPage iThank you from all of us at Sensata Technologies for purchasing this ACLD-40 controller. The ACLD-40 (also know as th

Seite 13 - ½” and ¾”)

Page 13 © 2015 Sensata TechnologiesInstallation2.4 General Wiring RequirementsThis section describes the requirements and recommendations for wiring

Seite 14

© 2015 Sensata TechnologiesPage 14Installation2.4.4 Wire Size and Overcurrent ProtectionThe wiring must be approved for the application (i.e., reside

Seite 15 - 2.0 Installation

Page 15 © 2015 Sensata TechnologiesInstallation2.6 ACLD Terminal Block ConnectionsThe ACLD controller has a ten-pole terminal block and a ground busb

Seite 16 - Installation

© 2015 Sensata TechnologiesPage 16InstallationBi-Directional Utility MeterUtility/GridPowerUtility Power DisconnectONOFFONOFFONOFFONOFFONOFFONOFFONOFF

Seite 17

Page 17 © 2015 Sensata TechnologiesInstallationMS-PAE Inverter/Charger(on MMPxxx-30D Enclosure with hood and backplate)ACLD-40DiversionControllerInver

Seite 18

© 2015 Sensata TechnologiesPage 18Installation2.8 Wiring the ACLDThe following steps are basic guidelines for installing and connecting wiring to and

Seite 19

Page 19 © 2015 Sensata TechnologiesInstallation2.9 ACLD Load RequirementsA diversion load is required to be connected to the ACLD. When the ACLD is a

Seite 20

© 2015 Sensata TechnologiesPage 20Installation2.9.2 Compatible Diversion LoadsBelow is a list of compatible loads that may be used with the ACLD.Info:

Seite 21 - 2.5 Torque Requirements

Page 21 © 2015 Sensata TechnologiesInstallation2.10 Connecting the ACLD to a MS-PAE Series InverterOne end of the ACLD/NETWORK cable plugs into the po

Seite 22

© 2015 Sensata TechnologiesPage 22Installation2.11 Using a Remote Control with the ACLD ControllerA remote control display (ME-ARC, ME-RC11, or ME-RTR

Seite 23

Safety InformationPage iiIMPORTANT PRODUCT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSTHIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE ACLD-40 CONTR

Seite 24

Page 23 © 2015 Sensata TechnologiesOperation3.0 Operation3.1 ACLD OperationNormally, when utility power is available, the grid-tie inverter in the sys

Seite 25 - 2.8 Wiring the ACLD

© 2015 Sensata TechnologiesPage 24OperationThe excess current is fi rst diverted to the primary diversion load, which could be sized to absorb the full

Seite 26 - 2.9 ACLD Load Requirements

Page 25 © 2015 Sensata TechnologiesOperation3.2 Three-Stage RegulationThe ACLD uses a three-stage process to help monitor the battery voltage (during

Seite 27

© 2015 Sensata TechnologiesPage 26OperationRelayPWMSwitchGrid-Tie InverterACLD Controller(Inactive)Renewable EnergyMS-PAE Series InverterBatteryBankBa

Seite 28

Page 27 © 2015 Sensata TechnologiesOperation3.4 Power Flow Scenarios - Utility Not ConnectedWhenever there is a utility power outage, the MS-PAE Seri

Seite 29

© 2015 Sensata TechnologiesPage 28OperationDuring a utility power interruption, the main household loads are no longer connected and the utility grid

Seite 30 - 3.0 Operation

Page 29 © 2015 Sensata TechnologiesOperationRelayPWMSwitchGrid-Tie InverterACLD Controller(Active)Renewable EnergyMS-PAE Series InverterBatteryBankBat

Seite 31 - Operation

© 2015 Sensata TechnologiesPage 30Operation3.5 Power Switch OperationPower Switch – The power switch on the right side of the ACLD (see Figure 1-2, i

Seite 32 - 3.2 Three-Stage Regulation

Page 31 © 2015 Sensata TechnologiesOperation3.7 Operating ModesOnce the ACLD load controller is powered and turned on, it has three normal operating m

Seite 33

© 2015 Sensata TechnologiesPage 32Operation3.9 ACLD StartupON/OFF Switch – The ACLD can be turned on and off by pressing the ON/OFF switch on the righ

Seite 34

Safety Information © 2015 Sensata TechnologiesPage iii CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONSCE MANUEL CONTIENT DES INSTRUCTIONS

Seite 35

Page 33 © 2015 Sensata TechnologiesTroubleshooting4.0 TroubleshootingThis section will help you troubleshoot the ACLD when it has a fault condition. T

Seite 36

© 2015 Sensata TechnologiesPage 34TroubleshootingTroubleshooting Continued:• Blinks On 5 times then off four seconds - Desat (i.e. Desaturation) Faul

Seite 37 - 3.6 Inverter Fan Operation

Page 35 © 2015 Sensata TechnologiesAppendix A – Specifi cations and Optional EquipmentAppendix A – Specifi cations and Optional EquipmentA-1 ACLD-40 Lo

Seite 38 - 3.7 Operating Modes

© 2015 Sensata TechnologiesPage 36Appendix A – Specifi cations and Optional EquipmentA-3 Optional Equipment and AccessoriesThe following components ar

Seite 39 - 3.9 ACLD Startup

Page 37 © 2015 Sensata TechnologiesAppendix B – Warranty & ServiceAppendix B – Warranty and Service B-1 Limited WarrantySensata Technologies warra

Seite 40 - 4.0 Troubleshooting

Page 38© 2015 Sensata TechnologiesNotes:

Seite 41 - Troubleshooting Continued:

Magnum-Dimensions ProductsManufactured by:Sensata Technologies2211 West Casino Rd.Everett, WA 98204Phone: 425-353-8833Fax: 425-353-8390 Web: www.magnu

Seite 42

Page iv© 2015 Sensata TechnologiesTable of Contents1.0 Introduction ... 11.1

Seite 43 - A-2 Regulatory Compliance

© 2015 Sensata TechnologiesPage vList of FiguresFigure 1-1, ACLD Inactive (Utility Power Available) ...

Seite 44 - B-1 Limited Warranty

Page vi© 2015 Sensata Technologies

Seite 45 - © 2015 Sensata Technologies

Page 1 © 2015 Sensata TechnologiesIntroduction1.0 IntroductionCongratulations on your purchase of the ACLD-40 (AC Load Diversion - 4.0kW) controller.

Seite 46

© 2015 Sensata TechnologiesPage 2IntroductionTraditionally, when a battery-based inverter is used, the renewable energy system is connected or ‘couple

Kommentare zu diesen Handbüchern

Keine Kommentare