2003 - Magnum Energy, Inc.
6
3. Operation, continued
Liquid Lead Acid (Flooded)
Bulk Absorption Float Equalize
14.6 VDC 14.6 VDC 13.4 VDC 15.5 VDC
GEL
Bulk Absorption Float Equalize
14.1 VDC 14.1 VDC 13.6 VDC Disabled*
AGM (Absorbed Glass Mat)**
Bulk Absorption Float Equalize
14.3 VDC 14.3 VDC 13.1 VDC 15.5 VDC
Chart 1 - Battery Charge Voltages
Battery Size Charge Time
200 AHr 90 minutes
400 AHr 120 minutes
600 AHr 150 minutes
800 AHr 180 minutes
1000 AHr 210 minutes
Function Default
Search 5 watts
LBCO 10 VDC
Battery Bank 400 AHr
Battery Type Liquid Lead Acid
Charge Rate 100 %
Contrast 75 %
Chart 2 - Absorption Times
(determined by battery bank size selection)
Chart 3 - Factory Default Settings
* CAUTION: Never “Equalize” Gel batteries.
** NOTE: AGM voltages are courtesy of Lifeline
TM
brand batteries.